Your fire safety responsibilities, in plain English
If you own, manage or control a non-domestic building, the law makes you the “responsible person” for fire safety. Here is what that means, and how often your fire safety equipment needs testing.
Who is the responsible person?
Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person is usually the employer, the owner, or whoever has control of the premises, such as a landlord, managing agent or facilities manager. In a shared building there may be more than one, and you must work together.
What the law asks you to do
- Have a suitable and sufficient fire risk assessment, and keep it up to date.
- Since October 2023, record the whole fire risk assessment and your fire safety arrangements in writing, whatever the size of your business, including the name of the person who carried it out.
- Use a competent person for your fire risk assessment if you do not have the knowledge in-house.
- Put the right fire safety measures in place: detection and alarms, emergency lighting, firefighting equipment, fire doors and clear escape routes.
- Keep those measures maintained in good working order, and keep records of testing and servicing.
- Give staff the information and training they need, and plan for emergencies, including fire drills.
How often should things be tested?
These are the usual intervals from the relevant British Standards. Your fire risk assessment may ask for something different, and that takes priority.
| Equipment | You (in-house) | A competent engineer |
|---|---|---|
| Fire alarm BS 5839-1 | Test a different call point every week and record it | Inspect and service at least every six months |
| Emergency lighting BS 5266-1 | Short functional test every month | Full-duration test every year |
| Fire extinguishers BS 5306-3 | Visual check every month | Service every year; extended service every 5 years (water, foam, powder) and every 10 years (CO2) |
| Fire doors | Regular checks that doors close fully and are not wedged open | Inspection by a competent person, typically every six months |
| Dry risers BS 9990 | Keep inlets and outlets clear and secure | Visual inspection every six months; pressure test every year |
| Fire dampers | – | Test at least every year |
| Smoke vents | Regular operational checks | Service at least every year |
| Fire drills and training | Fire drill at least once a year; training for new starters | Fire marshal and warden training |
Keep the evidence
If the fire service inspects, or something goes wrong, you will need to show that testing has been done. All of our maintenance customers get their certificates, service reports and defects online in the A&E Customer Portal, ready whenever you are asked.
Not sure where you stand?
We can review your building, tell you what is missing and put a single maintenance programme in place for everything on this page.